Flow Testing: High Rise Operations

Courtesy of Battalion Chief Mark Davis


This morning crews from Montgomery County Paramedic Engine 719, Paramedic Engine 728, and Battalion Chief 701 conducted several flow tests in high rise apartment buildings in the Gaithersburg area. MCFRS crews wanted to confirm the performance capabilities of their new pumpers and new high-rise fire hose and nozzles.  The goal was to obtain specific flows of 250 gpm and 500 gpm at specific pressures on the upper most part of the building using the building's standpipe system.


The roof proved to 
be the perfect place for flowing and measuring water and all four tests were completed without any problems.  
Each test involved a fire department pumper supplying water to standpipe system using the Fire Department Connection located on the front of the building near the lobby entrance. Supply pressures in excess of 220 psi were needed to meet the flow needs of the hose lines operation on the roof.  While 200+ psi might seem high, it is well within the operating range of a fire department pumper; these type of pressures are often needed to overcome the loss in system pressure due to the height of a building.

Many thanks go out to the Management and Maintenance Staff of the facilities for keeping their fire protection systems in good working order and for allowing MCFRS to complete this very important flow testing work.  Check out the videos below. 